Cookie Img
Back to top
Send SMS Send Inquiry
Home » Products » AC High Voltage » AC High Voltage Insulation Testing

AC High Voltage Insulation Testing

AC High Voltage Insulation Testing
Product Code : 09
Brand Name : RE
Price And Quantity
  • Minimum Order Quantity
  • 1
  • Unit of Measure
  • Piece/Pieces
  • Price Range
  • 150000 - 300000 INR
  • Minimum Order Quantity
Trade Information
  • FOB Port
  • Delhi
  • Payment Terms
  • Cash on Delivery (COD), Cash in Advance (CID), Cheque, Letter of Credit (L/C), Telegraphic Transfer (T/T)
  • Supply Ability
  • 10 Per Month
  • Delivery Time
  • 4 Week
  • Sample Available
  • Yes
  • Sample Policy
  • Contact us for information regarding our sample policy
  • Packaging Details
  • Bubble Rap Packing Wooden packing with water proof or as per customer requirement.
  • Main Export Market(s)
  • Asia, Australia, Central America, North America, South America, Eastern Europe, Western Europe, Middle East, Africa
  • Main Domestic Market
  • All India
  • Certifications
  • ISO 9001 : 2008 ISO : 14000
Product Description

Description

 

‘RE’ AC HV Rubber testing set is used for Testing Rubber Mats. These sets are generally used in Electrical manufacturing Industry/Power Houses, Electrical Repair etc. where AC H.V. test set is suggest by BIS or IEC. During AC H.V. testing High current is generated due to capacitive loading. AC High voltage test equipments are designed for continuous use, for testing, and can withstand short circuit. Fault burning can also be provided if desired.

 

Features

v Technologically advanced design that helped make proper use of space and minimize the size of the equipment.

v The equipment has been made so that it is very simple to operate, thus any person after learning once can operate it

 

 

 

Technical Specifications

 

AC High Voltage Insulation Test Set
Sr. No.ParametersDescription
1I/p Voltage 220/230V or 380/400V, 50/60HZ AC supply
2O/p VoltageUp 60KV and 100mA
3CapacityUp  to 6KVA
4Timer0-9999 Sec./min. Digital
5Control1- The unit can be manual/motorized control for voltage variation and push button controlled for HT actuation.
2-Selectror switch to select leakage current at 25%,50%,75% and 100% of the mA capacity required. 
3- The unit can be microprocessor based complete with on board memory, printout facility, programmable features etc.
4- The unit can be PLC based complte with computer, HMI memory, printer etc. for operation.
6MeteringVoltmeter : One Digital type connected on HT side to indicate the output voltage
Scale :  0-60 kV AC.
Ammeter : One Digital type ammeter Connected on earth side to indicate the leakage Current on sample under test.
Scale :  0-100mA 
7Protection A fast acting DC relay will isolate the circuit when the current exceeds pre-set level.
8InterlockingThe unit will have zero start interlocking to avoid the transients on HV transformer and provision for  cage door interlocking shall also be provided
9ConstructionAC High voltage test set consists of 
1) Control panel cum Regulating Transformer cum High Voltage Transformer.
9(a)Control Panel
Consist of :
LT ON Indicator , Push button to actuate HT, HT ON Indicator,Push button to deactuate HT, Fault Indicator (HT OFF Indicator), Push Button Switch to increase / decrease the output voltage, Tripping selector switch with tripping @ 10-15-20-25-30-35-40-50-60-70-80-90-100mA, Timer ON/OFF Switch, Switch for rate of rise @ 0.5kV/sec and 2kV/sec,  Timer Digital, Digital KV Meter, Digital mA Meter
 
9(b)Regulating TransformerContinuously variable transformer which feeds 0-230 V, to the main HV transformer. The voltage is boosted in ratio with transformer design. No wave shape distortion will take place. One terminal of HT transformer is maintained at earth potential through CST terminal, the other Ht terminal is brought out on suitable H.T. Load.
Protection:  The protective circuit incorporated in this unit consist of the following :
A) Zero Start Interlocking
B) Over current relay with current selection
C) Cage door at top side 
This prevents accidental start of unit after break down.
9(c)HV TransformerThe Main step up transformer is housed inside the body  supported with welded angle iron frame and the output has been brought out through  H.T.  Terminal.

RECTIFIERS & ELECTRONICS PVT. LTD.

Contact Us

( *represents compulsory fields )

Tips on getting accurate quotes. Please include product name, order quantity, usage, special requests if any in your inquiry.




RECTIFIERS & ELECTRONICS PVT. LTD.
10/3, DLF Industrial Area, Moti Nagar, New Delhi - 110015, India
Phone :+918286086347
Fax :91-11-25438460/41425853
Mr. Manish Arora (Director)
Mobile :+918286086347
Trust Stamp
Product Showcase
Send SMS Send Inquiry